67
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Eeab11
Pump Management Setpoint: Setpoint if HR1 pump is regulated by temperature
55
°C/°F
Kp:
Kp if HR1 pump is regulated by temperature
1
%/°C
Integral time:
Integral time if HR1 pump is regulated by temperature
120
s
Eeab13
HR1 enable HR probe temp.
Filter:
Enable multiple measurements of temperature probe
No
YES | NO
Number of samples
Number of samples
1…200
Eeab14
Max. water temp. Alarm
thresh:
Maximum water temperature Alarm threshold
85
°C/°F
Diff erential:
Diff erential for maximum water temperature Alarm threshold
5
°C/°F
Eeab15
HR2 Regulation type:
Diff erent type of regulation of fi rst heat reclaim
Temperat.
External Signal
Temperature
Digital Input
Setpoint
Setpoint if HR2 is regulated by temperature
40
°C/°F
Kp:
Kp if HR2 is regulated by temperature
1
%/°C
Integral time:
Integral time if HR2 is regulated by temperature
200
s
Eeab16
HR2 Valve type:
Type of valve of fi rst heat reclaim
ON/OFF
ON | OFF | 0
| 10V
Activation thr:
Threshold to activate valve output HR2
10.0
%
De-activat thr:
Threshold to de-activate valve output HR2
5.0
%
Activation delay:
Delay to activate valve output HR2
30
s
Eeab17
En. Pump:
Enable pump of fi rst heat reclaim
No
YES | NO
Pump type:
Selection of pump type of fi rst heat reclaim
Modulating | ON
| OFF
Pump delay off :
Delay to switch off pump HR2
0
s
Eeab18
Pump regulation type:
Diff erent type of pump regulation of fi rst heat reclaim
HR request
HR request |
Diff temperature
On threshold:
Threshold to activate pump output HR2
5.0
%
Off threshold:
Threshold to de-activate pump output HR2
0.0
%
Eeab19
Pump Management Setpoint: Setpoint if HR2 pump is regulated by temperature
55
°C/°F
Kp:
Kp if HR2 pump is regulated by temperature
1
%/°C
Integral time:
Integral time if HR2 pump is regulated by temperature
120
s
Eeab20
HR2 enable HR probe temp.
Filter:
Enable multiple measurements of temperature probe
No
YES | NO
Number of sample
Number of samples
1…200
Eeab21
Maximum water temp. Alarm
thresh:
Maximum water temperature Alarm threshold
85
°C/°F
Diff erential:
Diff erential for maximum water temperature Alarm threshold
5
°C/°F
Eeab25
Actions on HPV valve and gas
cooler fans setpoints done in:
Type of HPV setpoint increment
Simultan.
Mode
Simultaneous
Sequential mode
with Threasold
Wait. Time to act:
Delay to start HPV setpoint increment
120
s
Eeab26
En. GasCool.bypass:
Enable Gas Cooler bypass
No
YES | NO
Gas cooler bypass 3way
valve type:
Gas cooler bypass 3way valve type
0/10
V
0 | 10 | ON | OFF
Valve Mode
Bypass valve mode
ON/OFF
Modulating
ON | OFF
Eval. Time to byp:
Evaluation time to start GC bypass
30
s
Max receiver press.
To allow byp:
Max receiver pressure to allow bypass
60.0
barg
Eeab28
HPV valve modul. Setp.min%: Min. HPV setpoint with heat reclaim total request upper setted threshold
75.0
barg
HPV valve modul. Setp.100%: Max. HPV setpoint with heat reclaim total request equal to 100%
85.0
barg
Time to min setp.:
Time to reach minimum setpoint
60
s
Incr. Step:
Value of incremental step between setpoint min& e setpoint 100%
0.5
barg
Wait time:
Time each step
60
s
Eeab29
Gas cool. Fans modulat. Incr.
Step:
Value of GC incremental step
1.0
°C/°F
Gas cool. Fans modulat. Wait
time:
Time each step
60
s
Gas cool. Fans modulat. Max
off set:
GC maximum off set
5.0
°C/°F
Gas cool. Fans modulat. Min.
HR request:
Minimum HR total request to start GC action
30.0
%
Gas cool. Fans modulat. Diff .
OFF:
Diff erential to decrease GC action
5.0
%
Eeab30
Max decrease time of HPV
off set:
Time to decrease total HPV off set
240
s
Max decrease time of GC
off set:
Time to decrease total GC off set
120
s
Max t.close byp.
Time to close bypass valve
120
s
Efa05
Min.HR request:
Enable generic stage function 1
30.0
%
Diff .OFF:
…
5.0
%
JAN.funct.5
Enable generic stage function 5
disable
---
disable | enable
Efa06
Regulation variable
Regulation variable for stage 1 generic function
---
---
…
Mode
Direct or reverse regulation
direct
---
direct | Reverse
Efa07
Enable
Enabling variable for stage 1 generic function
---
---
…
Description
Enable description change
skip
---
skip | change
---------------
---------------
---
---
…
Efa08
Setpoint
Setpoint stage 1 generic function
0.0 °C
…
… (**)
Diff erential
Stage 1 generic function diff erential
0.0 °C
…
… (**)
Efa09
High alarm
High alarm enabling for stage 1 generic function
disable
---
disable | enable
High alarm
High alarm threshold for stage 1 generic function
0.0 °C
…
… (**)
Delay
High alarm delay for stage 1 generic function
0
s
0…9999
Alarm type
High alarm type for stage 1 generic function
Normal
---
Normal | Serious
Low alarm
Low alarm enabling for stage 1 generic function
disable
---
disable | enable
Low alarm
Low alarm threshold for stage 1 generic function
0.0 °C
…
… (**)
Delay
Low alarm delay for stage 1 generic function
0
s
0…9999
Alarm type
Low alarm type for stage 1 generic function
Normal
---
Normal | Serious
…
…
…
…
…
…
Efb05
JAN.modulat.1
Enable generic modulating function 1 management
disable
---
disable | enable
JAN.modulat.2
Enable generic modulating function 2 management
disable
---
disable | enable
Efb06
Regulation variable
Regulation variable for generic modulating function 1
---
---
…
Mode
Direct or reverse regulation
direct
---
Direct | Reverse
Efb07
Enable
Enabling variable for generic modulating function 1
---
---
…
Description
Enable description change
Skip
---
skip | change
---------------
---------------
---
---
…
Efb08
Setpoint
Setpoint for generic modulating function 1
0.0 °C
…
… (**)
Diff erential
Diff erential for generic modulating function 1
0.0 °C
…
… (**)
Page 116 of 172
Copyright HPL March 2021
P4114S Rev 03
Содержание Hubbard GCU2040PXB1
Страница 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 44: ...4 Wiring Schematics Model GCU2040PXB1 Part Number D4155S Page 44 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 161: ...8 PRESSURE ENTHALPY DIAGRAM FOR R744 REFRIGERANT Page 161 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...