pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
According to the number of alarms selected, the default associated
descriptions will be as shown in the table.
L1-Alarms ALC90
L1-Generic alarm comp.
C01:
C02:
C03: -
Further example:
L1-Alarms ALC92
L1-High press.al.comp.
C01: -
C02: -
C03:
The same applies to the following alarms:
•
L1 – Compressors overload alarm
•
L1 – Compressors high pressure
•
L1 – Compressors low pressure
•
L1 – Compressors oil alarm
•
L2 – Compressors generic alarm
•
L2 – Compressors overload alarm
•
L2 – Compressors high pressure
•
L2 – Compressors low pressure
•
L2 – Compressors oil alarm
Default descriptions
b
ased on the num
b
er of alarms
Num
b
er of alarms
Descriptions
1
Generic
2
Overload
HP-LP
3
Overload
HP-LP
Oil
4
Overload
HP
LP
Oil
Tab. 8.b
Note
: for oil alarms, special management is available whereby the
alarm is interpreted as an oil level alarm. When the alarm is
activated, a number of attempts are made to restore the level for a set
time before the alarm is signalled and the compressor stopped.
If a modulating device is used for the compressors, further alarms
become available:
•
compressor inverter warning, common for the entire suction line,
when the device is an inverter
•
oil sump temperature alarm, high discharge temperature and oil
dilution, for Digital Scroll™ compressors
For each compressor, two alarm variables are sent to the supervisor, one
for each priority. As well as the alarm signal, the description of the alarm is
also sent to the supervisor, using the values shown in the table:
The supervisor can interpret the variables sent by pRack PR300T and
provide the correct description of the alarm.
8.3 Pressure and prevent alarms
pRack PR300T can manage pressure alarms from a pressure switch or
probe, according to the following diagram.
Alarms from pressure switch:
•
Low suction pressure
•
High condensing pressure
Alarms from probe:
•
Low suction pressure
•
High suction pressure
•
Low condensing pressure
•
High condensing pressure
One possible example for the low pressure alarms is shown in the fi gure:
Pressure
Pro
b
e
a
l
arm
Pressostat
a
l
arm
LP
Di
ff
erentia
l
Fig. 8.c
In addition, the high pressure alarm features a prevent function, available
by manually overriding the devices as well as using additional functions,
such as heat recovery and ChillBooster. Operation of the alarms and
prevent function is described below.
8.3.1
Pressure alarms from pressure switch
The parameters corresponding to these alarms can be set in branch
G.c.a/G.c.b of the main menu.
Low suction pressure from pressure switch
The low suction pressure alarm from pressure switch has the eff ect of
stopping all the compressors without observing the various times,
therefore when the digital input confi gured as low pressure switch
is activated, all the compressors on the line aff ected are stopped
immediately.
This alarm features semiautomatic reset, and both the monitoring time
and the number of activations in the specifi ed period can be set. If the
number of activations is higher, reset becomes manual.
In addition, the delay after which the alarm is activated on both start-up
and during operation can be set.
The delay at start-up only applies to unit start-up and not compressor
power-up.
H
igh condensing pressure from pressure switch
The high condensing pressure alarm from pressure switch has the eff ect
of stopping all the compressors without observing the various times
and forcing the fans on at maximum speed, therefore when the digital
input confi gured as high pressure switch is activated, all the compressors
on the line aff ected are stopped immediately and the fans operate at
maximum output.
This alarm features manual or automatic reset, as confi gured by the user.
The delay after which the alarm is activated can also be set
Page 133 of 172
Copyright HPL March 2021
P4114S Rev 03
Содержание Hubbard GCU2040PXB1
Страница 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 44: ...4 Wiring Schematics Model GCU2040PXB1 Part Number D4155S Page 44 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 161: ...8 PRESSURE ENTHALPY DIAGRAM FOR R744 REFRIGERANT Page 161 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...