Si12-411A
Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)
Removal Procedure
243
2.2
Removal of
Electrical BOX
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1. Removing the tie wires
Remove the piping in the
backward direction.
1
The figure shows the tie
pipe connections.
2
Remove the terminal
board fitting screw.
Match the colours of the tie
wires to A, B, C and D ports
as follows.
(1) - Black Power
(2) - White Power
(3) - Red Transmission
Wires are fixed to the
terminal board with screws.
Terminal board is made of
integral moulded resin.