Si12-411A
Outdoor Unit (80 / 90 Class)
Removal Procedure
235
1.7
Removal of
Sound Insulation
and
Reactor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
Release the clip fixing
the compressor lead
wire.
2
Remove 2 screws of
the partition board, and
move the board
leftward.
The partition board is not
removable as it is fixed with
the fitting screw in the rear
bottom.
3
Remove the noise
insulation (outer).
Carefully remove the noise
insulation, which is easily
torn in the piping section.