Si12-411A
Control Specification
Function and Control
107
3.16 Additional Function
3.16.1
Connection Pipe Condensation Preventing Function
This control is intended to adjust the electronic expansion valve opening so that the outdoor unit
gas pipe temperature (GDN) be kept below 8°C.
3.16.2
Priority Room Setting
Electronic expansion valves are controlled to provide the unit designated as the priority room
with the capacity of other room units.
(Distribution of capacity: Priority room unit ---
∆
D Max., other room units ---
∆
D -
α
)
Setting method
Turn off the circuit breaker before changing the setting.
Only one room can be set as the priority room.
Control start conditions
Priority room setting is made.
AND
“Powerful” signal from the priority room unit is received.
Note:
The operation mode of the priority room unit has precedence.
Cancellation of control
The control function is canceled when the “Powerful” operation mode is switched off or 20
minutes elapse after “Powerful Operation” started.
3.16.3
Powerful Operation Mode
Compressor operating frequency is increased to PI Max. (Max. Hz of operating room unit
Σ
S)
and outdoor unit airflow rate is increased.
3.16.4
Voltage Detection Function
Power supply voltage is detected each time equipment operation starts.
C
room
B
room
A
room
Living
room
C
room
B
room
A
room
Living
room
When Inverter
powerful-operation
is selected in the
priority room
Normal
operation
(R1396)
Содержание FTKE25BVM
Страница 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Страница 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Страница 7: ...Si12 411A vi Table of Contents...
Страница 67: ...Specifications Si12 411A 56 Specifications...
Страница 81: ...Printed Circuit Board Connector Wiring Diagram Si12 411A 70 Printed Circuit Board Connector Wiring Diagram...
Страница 131: ...Instruction Si12 411A 120 System Configuration CDK X D 25 35 50 60 C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2...
Страница 173: ...Instruction Si12 411A 162 System Configuration...
Страница 227: ...Check Si12 411A 216 Service Diagnosis...
Страница 268: ...Si12 411A Others 257 Part 8 Others 1 Others 258 1 1 Test Run from the Remote Controller 258 1 2 Jumper Settings 259...
Страница 295: ...Si12 411A iv Index...
Страница 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...