Si12-411A
Troubleshooting
Service Diagnosis
181
5.10
Freeze-up Protection Control
Remote
Controller
Display
A5
Outdoor Unit LED
Display
A
5
1
4
2
1
3
4
4
4
Method of
Malfunction
Detection
Indoor unit icing, during cooling operation, is detected by checking the temperatures sensed by
the indoor unit heat exchanger thermistor and room temperature thermistor that are located in a
shut-down room.
Malfunction
Decision
Conditions
In the cooling mode, the following conditions (A) and (B) are kept together for 5 minutes.
(A) Indoor unit heat exchanger temperature
≤
–1°C
(B) Indoor unit heat exchanger temperature
≤
Room temperature –10°C
If the indoor unit icing protector is activated four times straight, the system will be shut down.
(The 4-time counter will reset itself if any of the following errors does not occur during the
compressor running time (total time): OL, radiation fin temperature rise, gas shortage, and
compressor startup.)
<Total 60 minutes>
Supposed
Causes
Wrong wiring or piping
Ev malfunctioning in each room
Short-circuit
Indoor unit heat exchanger thermistor defective
Indoor unit thermistor defective
Содержание FTKE25BVM
Страница 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Страница 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Страница 7: ...Si12 411A vi Table of Contents...
Страница 67: ...Specifications Si12 411A 56 Specifications...
Страница 81: ...Printed Circuit Board Connector Wiring Diagram Si12 411A 70 Printed Circuit Board Connector Wiring Diagram...
Страница 131: ...Instruction Si12 411A 120 System Configuration CDK X D 25 35 50 60 C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2...
Страница 173: ...Instruction Si12 411A 162 System Configuration...
Страница 227: ...Check Si12 411A 216 Service Diagnosis...
Страница 268: ...Si12 411A Others 257 Part 8 Others 1 Others 258 1 1 Test Run from the Remote Controller 258 1 2 Jumper Settings 259...
Страница 295: ...Si12 411A iv Index...
Страница 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...