Troubleshooting
Si12-411A
170
Service Diagnosis
5.2
Outdoor Units
4
: ON,
1
: OFF,
5
: Blinks
Green : Flashes when in normal condition
Red : OFF in normal condition
- : Not used for troubleshooting
∗
: Varies depending on the cases.
Note:
1. The indications in the parenthesis ( ) in the remote controller display column are displayed
only when system-down occurs.
2. When a sensor error occurs, check the remote controller display to determine which sensor
is malfunctioning.
If the remote controller does not indicate the error type, conduct the following operation.
*Turn the power switch off and back on again. If the same LED indication appears again
immediately after the power is turned on, the fault is in the thermistor.
*If the above condition does not result, the fault is in the CT.
3. The indoor unit error indication may take the precedence in the remote controller display.
Outdoor Unit LED Indication
Indication on
the remote
controller
Description of The Fault
Details of
Fault (Refer
to the
indicated
page.)
Green
Red
A
1
2
3
4
5
3
3
3
3
00
Outdoor unit in normal condition
(Conduct a diagnosis of the indoor unit.)
—
UA
Unspecified voltage (between indoor and outdoor units)
UH
Anti-icing function in other rooms
5
3
3
4
4
(
U0
)
Insufficient gas
5
4
3
4
3
(
E5
)
OL activation (compressor overload)
5
3
4
4
3
(
E6
)
Compressor lock
5
4
3
4
3
F3
Discharge pipe temperature control
5
3
3
3
4
L4
Radiation fin temperature rise
(Protection of driver overheating)
5
4
4
3
3
H8
CT or related abnormality
5
4
4
3
3
H6
Position sensor abnormality
H9
Outdoor air thermistor or related abnormality
J3
Discharge pipe thermistor or related abnormality
J6
Heat exchanger thermistor or related abnormality
J8
Liquid pipe thermistor or related abnormality
J9
Gas pipe thermistor or related abnormality
P4
Radiation fin thermistor or related abnormality
5
3
3
4
3
L5
Output over current detection
5
3
4
3
4
E8
Input over current detection
5
4
3
4
4
A5
Freeze-up protection control
5
4
4
4
4
E7
DC fan lock
5
4
3
3
3
EA
Four way valve abnormality
5
4
4
3
4
L3
Electrical box temperature rise
5
4
3
3
4
U2
Low-voltage detection
Содержание FTKE25BVM
Страница 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Страница 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Страница 7: ...Si12 411A vi Table of Contents...
Страница 67: ...Specifications Si12 411A 56 Specifications...
Страница 81: ...Printed Circuit Board Connector Wiring Diagram Si12 411A 70 Printed Circuit Board Connector Wiring Diagram...
Страница 131: ...Instruction Si12 411A 120 System Configuration CDK X D 25 35 50 60 C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2...
Страница 173: ...Instruction Si12 411A 162 System Configuration...
Страница 227: ...Check Si12 411A 216 Service Diagnosis...
Страница 268: ...Si12 411A Others 257 Part 8 Others 1 Others 258 1 1 Test Run from the Remote Controller 258 1 2 Jumper Settings 259...
Страница 295: ...Si12 411A iv Index...
Страница 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...