Si12-411A
Troubleshooting
Service Diagnosis
185
5.13 DC Fan Lock
Remote
Controller
Display
E7
Outdoor Unit LED
Display
A
5
1
4
2
4
3
4
4
4
Method of
Malfunction
Detection
A fan motor line error is detected by checking the high-voltage fan motor rpm being detected by
the Hall IC.
Malfunction
Decision
Conditions
The fan does not start in 30 seconds even when the fan motor is running.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Supposed
Causes
Fan motor breakdown
Harness or connector disconnected between fan motor and PCB or in poor contact
Foreign matters stuck in the fan
Troubleshooting
Check No.15
Refer to P.214
Turn off the power and
reconnect the connector.
Remove.
Replace the outdoor unit
fan motor.
Replace the outdoor unit
PCB.
(R2843)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Fan motor connector
disconnected?
YES
YES
NO
YES
NO
Pulse signal inputted?
NO
Foreign matters in or
around the fan?
Get started.
Check No. 15
Check the outdoor unit PCB rpm
pulse input.
Содержание FTKE25BVM
Страница 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Страница 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Страница 7: ...Si12 411A vi Table of Contents...
Страница 67: ...Specifications Si12 411A 56 Specifications...
Страница 81: ...Printed Circuit Board Connector Wiring Diagram Si12 411A 70 Printed Circuit Board Connector Wiring Diagram...
Страница 131: ...Instruction Si12 411A 120 System Configuration CDK X D 25 35 50 60 C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2...
Страница 173: ...Instruction Si12 411A 162 System Configuration...
Страница 227: ...Check Si12 411A 216 Service Diagnosis...
Страница 268: ...Si12 411A Others 257 Part 8 Others 1 Others 258 1 1 Test Run from the Remote Controller 258 1 2 Jumper Settings 259...
Страница 295: ...Si12 411A iv Index...
Страница 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...