Service Check Function
SiBE12-816_D
209
Service Diagnosis
3.2
SA Indoor Unit - FFQ Series
3.2.1 Relations between Modes
The following modes can be selected by using the [Inspection / Test] button on the remote
controller.
3.2.2 BRC1D528
If operation stops due to malfunction, the operation lamp on the remote controller blinks, and
error code is displayed. (Even if stop operation is carried out, malfunction contents are
displayed when inspection mode is entered.) The error code enables you to tell what kind of
malfunction caused operation to stop.
Refer to page 213, 214 for error code and malfunction contents.
Note:
1. When you press the [Inspection / Test] button, the inspection display blinks.
2. While in the inspection mode, press the [ON/OFF] button for 5 seconds or more to clear the
failure history indication. In this case, the error code blinks twice and then changes to “
00
” (=
Normal), the UNIT No. changes to “
0
”, and the operation mode automatically switches from
the inspection mode to the normal mode (displaying the set temperature).
Press the
[Inspection / Test]
button once.
(R11277)
Press the
[Inspection / Test]
button once.
After 10 seconds
Thermostat is forcibly turned on.
Press the
[Inspection / Test]
button for more than 4 seconds.
Field
setting
mode
Service
mode
Normal
mode
Trial
operation
mode
Inspection
mode
Press the
[Inspection / Test]
button once.
Press the
[Inspection / Test]
button for more than 4 seconds.
Press the
[Inspection / Test]
button once
or leave the remote controller untouched
for 30 minutes.
Indoor unit settings can be made.
z
Filter cleaning sign time
z
Others
Service data can be obtained.
z
Error code history
z
Temperature data of various sections
Service settings can be made.
z
Forced fan ON
z
Airflow rate setting
Following codes can be checked.
z
Error codes
z
Indoor model code
Operation lamp
[ON/OFF] button
(R14423)
Inspection display
Display of indoor unit
for which a malfunction
has been detected
[Inspection / Test] button
Error code
Содержание 2MKS40G2V1B