Field Settings
SiBE12-816_D
309
Trial Operation and Field Settings
4.2.2 Overview of the Field Settings
: factory setting
Note:
Any function that is not available on the indoor unit is not displayed.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01
02
03
04
10
(20)
0
Filter cleaning
sign interval
Ultra
longlife
filter
Li
ght
Approx.
10,000
hrs.
He
a
v
y
Approx.
5,000
hrs.
—
—
Longlife
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
1
Longlife filter type
Longlife
filter
Ultra
longlife filter
—
—
2
Remote controller thermistor
Enabled
Disabled
—
—
3
Filter cleaning sign
Display
No display
—
—
11
(21)
0
Indoor unit number of
simultaneous operation
system
Pair
Twin
Triple
Double twin
1
Simultaneous operation
system individual setting
Unified
setting
Individual
setting
—
—
7
External static pressure
setting
Airflow
adjustment
is OFF
Completion
of airflow
adjustment
Start of
airflow
adjustment
—
12
(22)
1
Forced ON/OFF function
Forced
OFF
ON/OFF
operation
—
—
2
Thermostat differential
changeover (setting for when
using remote sensor)
1°C
0.5°C
—
—
13
(23)
0
High air outlet velocity (for
high ceiling applications)
≤
2.7 m
2.7 ~ 3.0 m
3.0 ~ 3.5 m
—
1
Selection of airflow direction
(setting for when a blocking
pad kit has been installed)
4-way flow
3-way flow
2-way flow
—
3
Selection of airflow function
(setting for when using a
decoration panel for outlet)
Equipped
Not equipped
—
—
4
Airflow direction range setting
Upper
Normal
Lower
—
6
External static pressure
Standard
High
Low
—
15
(25)
3
Drain pump operation with
humidifying
Not equipped
Equipped
—
—