Troubleshooting with LED
Service Diagnosis
198
BRC7E530W/531W
In case of wireless remote controller, a signal receiver PCB and a display PCB are installed on
indoor unit.
When the error occurs, the operation lamp on the display PCB blinks.
Caution:
When operation stops suddenly and the operation lamp blinks, it could be "operation mode
conflict".
Check followings;
Are the operation modes all the same for the indoor units connected to multi system outdoor
unit?
If not, set all the indoor units to the same operation mode and confirm that the operation lamp is
not blinking.
Moreover, when the operation mode is automatic, set all the indoor unit operation mode as
"cooling" or "heating" and check again if the operation lamp is normal.
If the lamp stops blinking after the above steps, there is no malfunction.
★
Operation stops and operation lamp blinks only for indoor unit which different operation mode
is set later. (The first set operation mode has priority.)
Service Monitor
The indoor unit has one green LED (LED A) on the control PCB. When the microcomputer
works in order, the LED A blinks.
1.2
Outdoor Unit
The outdoor unit has one green LED (LED A) on the PCB. When the microcomputer works in
order, the LED A blinks.
BRC1D528
Operation lamp (red)
(R14422)