The network protector breaker failing to close or trip during these minimum voltage series of tests can
indicate a mechanism or trip device that needs immediate attention. Records should be made of the
minimum voltage values so that a year-to-year comparison can be made. Slow deterioration of the
motor or trip device can be observed over the years by making such comparisons. Pin pointing such
problems in advance can lead to lower maintenance costs over the life of the equipment.
Rated Voltage
L-L
Or
L-G
Control Relay Closing Motor
80-106% 78-106%
Tripping Voltage
7.5-106%
125/216
L-L
170-230 157-230
16-230
277/480
L-G
220-295 200-295
36-510 *
277/480 or 480
L-L
385-510 350-510
36-510
* Trip coil connected L-L