I.B.
35-557
39 of 45
TABLE 1 – SUGGESTED RELAY SETTINGS
When using the HWT-500 test set to calibrate relays mounted on the network protector breaker, the settings
listed below will satisfy the majority of dedicated feeder, distributed grid or spot network applications. In some
cases, however, it may be necessary or advisable to modify these adjustments to meet particular system
conditions (such as where the network units are supplied from non-dedicated primary feeders or where there
exists an unusual relationship between the primary feeders).
216Y/125 Volt Network Protectors
Master Relay
Reverse Current at 180 degrees (protector breaker closed):
Trip contact makes at 0.2% of protector current transformer rating.
Overvoltage close at 0 degrees (protector breaker open):
Close contact makes at 1.5 volts.
Phasing Relay
Overvoltage close at 60 degrees (protector breaker open):
Contact open at 0.0 volts <-IMPORTANT
Contact closed at 0.5 volts.
480Y/277 Volt Network Protectors
Master Relay
Reverse current at 180 degrees (protector breaker closed):
Trip contact makes at 0.2% of protector current transformer rating.
Overvoltage close at 0 degrees (protector breaker open):
Close contact makes at 3.3 volts.
Phasing Relay
Overvoltage close at 60 degrees (protector breaker open):
Contact open at 0.0 volts <- IMPORTANT
Contact closed at 0.5 volts.
NOTE
WHEN 216-VOLT RELAYS WITH POTENTIAL AUTOTRANSFORMERS ARE USED ON
480-VOLT PROTECTORS, THE 216-VOLT RELAYS ACTUALLY “SEE” THE ABOVE
VOLTAGE DIVIDED BY 2.2.