I.B.
35-557
27 of 45
Trip Test
All of the switch positions remain the same as used in the “Close Test” with exception of the Phasing
switch and the I&PV switch which must be changed to the 180 position and the AI position,
respectively. The network protector must be closed.
By rotating the VARIAC you can increase the reverse current value to the desired value at which the
MPC TRIP light becomes illuminated. The network protector will then open its main contacts. Note
the MPC TRIP light will remain illuminated for approximately 1 second during which time the network
protector breaker must open its main contacts. After the 1-second interval the FLOAT light will again
be illuminated. The network protector breaker should be tripped several times to ensure that the
operation is consistent.
For testing the MPCR or MPCV, DO NOT remove any of the relay terminal screws or connect the
COMM-RED-GREEN cable assembly. To do so will not permit the relay to receive its required input
signals.
Phase Detection Test
All of the switch positions remain the same as used in the “Close Test”. The MPCR or MPCV “PL”
setting must be set to +5 degrees.
By rotating the VARIAC you can increase the overvoltage phasing value. The value chosen should
be somewhat above that value which operated the network protector breaker in the MPC “Close
Test”. The MPC must not make it close contact. By changing the MPC “PL” setting back to the
original –5 degree setting, the relay should once again make its close contact.