I.B.
35-557
13 of 45
16. Rotate the Supply Voltmeter switch checking all phase-to-phase and phase-to-ground voltages.
Return the Supply Voltmeter to the CA position.
17. Rotate the Phasing Volts Switch to the “ON” position.
18. Confirm that the breaker main contacts are open.
19. Turn the VARIAC knob clockwise to slowly increase the phasing volts. When the protector
closes observe the value of the phasing volts and return the VARIAC to the zero position.
NOTE: The voltmeter requires some time to adjust to lower voltage inputs. Please adjust
the voltmeter slowly when measuring small values of phasing volts. You will also note that
because of residual non-zero voltage across the VARIAC the voltmeter does not register
true zero volts.
20. With the protector closed you are now ready to perform a reverse current trip test.
21. Rotate the Phasing Volt switch counterclockwise to its “OFF” position.
22. Place the Phasing Switch to the 180-degree position.
23. Place the I & PV Switch to any one of AI, BI or CI positions.
24. Turn the VARIAC knob clockwise to slowly increase the reverse current. When the protector
trips observe the value of the trip current on the Ammeter and return the VARIAC to the zero
position.
25. If the network protector relay is found to be within your specified calibration you can proceed to
the Mechanical Component Test (Cutler-Hammer on page 23, General Electric on page 36).
The mechanical tests are performed to ensure that the motor, tripping device and intermediate
motor control device are operating at the minimum pick-up voltages.
NOTE: Because of the ruggedness of the HWT-500 design and the components selected, it
is possible to perform crossed phase, rolled phase and shorted phase tests using this
device so long as the breaker main contacts are in the open position and motor closing has
been blocked. Unintentional closures under these conditions will clear the 15 amp fuses
located on the front panel of the test set.
NOTE: The electrical interlock produces a noticeable hum in the 216 volt position and
is a
normal condition of operation
.