I.B.
35-557
37 of 45
The network protector breaker failing to close or trip during these minimum voltage series of tests can indicate
a mechanism or trip device that needs immediate attention. Records should be made of the minimum voltage
values so that a year-to-year comparison can be made. Slow deterioration of the motor or trip device can be
observed over the years by making such comparisons. Pin pointing such problems in advance can lead to
lower maintenance costs over the life of the equipment.
Rated Voltage of Network
Protector
L-L
Control Relay Closing Motor
90-106% 73-106%
Tripping Voltage
7 ½ - 106 Percent
125/216
L-L
170-230 157-230
16-230
277-480
L-G
220-295 200-295
36-510 *
277/480 or 480
L-L
385-510 350-510
36-510
* Trip coil connected line-to-line