SUGGESTED TRIP SETTINGS
These values are based on a setting of 0.2% of the protector current transformer rating. The chart
below lists the standard ratio of C.T. which would be supplied for any given network protector rating.
Be alerted, however, that network protector current transformers, and their ratios, may have been
changed at the time of manufacture, upon request, or may have been changed after installation.
Ampere Protector
Ratings
CT Ratio
Ampere Suggested Trip
Setting at 180
800 800/5
1.6
1200 1200/5
2.4
1600 1600/5
3.2
1875 1600/5
3.2
2000 2000/5
4.0
2250 2000/5
4.0
2500 2500/5
5.0
2825 2500/5
5.0
3000 3000/5
6.0
3500 *
3000/5
6.0
4500 3000/5
6.0
* G.E. 3500A Network Protectors are normally supplied with 3500/5 ratio C.T.’s.