I.B.
35-557
33 of 45
GENERAL ELECTRIC TYPE SSNPR SOLID STATE RELAY
Before commencing work, refer to the Safety Information
CAUTION
THE SSNPR RELAY SWITCHES AN AC VOLTAGE THROUGH ITS TRIP AND CLOSE
CONTACTS; FOR THIS REASON, DO NOT CONNECT THE “COMM-RED-GREEN” INDICATOR
LEADS.
Switch Positions
Network protector open and set for automatic operation.
FUNCTION Switch – “RELAY” position
I & PV Switch – PVA position for close, AI for trip
Supp VM Switch – CA position
PHASE switch –0 position for close, 180 for trip
Single PH Test Switch – OFF
VARIAC – zero position
SUPPLY Switch – 216 or 480 position depending on network system voltage
NOTE – Make certain that the phasing adjustment of the SSNPR is in the –5 degrees range before
commencing the Close Test.