I.B.
35-557
23 of 45
MECHANISM COMPONENT TESTS
Before commencing work, refer to the Safety Information.
Switch Positions
Network protector open and set for automatic operation with the relays removed.
FUNCTION Switch – “MECH” position
I & PV Switch – AI position
Supp VM Switch – CA position PHASE
switch
–0
position
Single PH Test Switch – OFF
VARIAC – zero position
PHASE volt switch – OFF position
SUPPLY Switch – 216 or 480 position depending on network system voltage
In this test, voltage is controlled by the variable autotransformer. Before commencing the test,
remove the BN relay (if applicable) and replace it with a BN dummy or jack plate assembly. You must
know the general breaker wiring configuration for the motor close and trip circuits. For example, you
must know whether the motor is connected phase-to-phase or phase-to-ground as well as the trip
device. This information can best be obtained from the wiring diagram of the network protector
breaker under test.
For mechanical closing operation the Supply VM switch should be in the CA position and should read
near zero potential with the VARIAC at zero. This is based on breakers that have the closing motor
wired C to A phase and the reading on the VOLTMETER reflects voltage applied between cable
terminal TC and TA. Closing values for both line-to-line and line-to-neutral wired breakers are
indicated on the charts located on page 24.
By turning the VARIAC control knob clockwise, increase the voltage displayed on the VOLTMETER.
Set the voltage to the minimum close level and depress the red (close) push button. The breaker
must close its contacts at the minimum voltage level. Return the VARIAC to the zero position.