BN DE-SENSITIZING RELAY INSTANTANEOUS TRIP TEST
Before commencing work, refer to the Safety Information.
Switch Positions
Network protector position is immaterial.
FUNCTION Switch – “RELAY” position
I & PV Switch – AI position
Supp VM Switch – CA position
PHASE switch – 180 position
Single PH Test Switch – A
VARIAC – zero position
SUPPLY Switch – 216 or 480 position depending on network system voltage
By increasing the VARIAC’S position you can increase the reverse current value to the desired
current level. If the test current is passed directly through the primary winding of the current
transformers on the network protector breaker, any setting within the range of the relay can be
obtained by utilizing the VARIAC. When the test current is passed directly through the primary
winding of the current transformers, 5 amperes represents 100% load current. The BN relay
instantaneous trip elements are non-directional, so direction of current flow is immaterial. One
instantaneous trip elements is connected between terminals 7 and 8 of the relay; another between
terminals 9 and 10, and the third between terminals 11 and 12. Test current is supplied to each trip
element in turn and the setting of the elements is indicated when the green light is illuminated. A
maximum of 20 amperes is available for this test.