OVERALL CLOSE AND TRIP TEST CONNECTION
Before commencing work, refer to the Safety Information.
Close Test – Switch positions
Network protector open and set for automatic operation
FUNCTION Switch – “RELAY” position
I & PV Switch – PVA position
Supp VM Switch – CA position
PHASE switch – 60 position
Single PH Test Switch – OFF position
PHASING volt switch – ON position VARIAC – zero position
SUPPLY Switch – 216 or 480 position depending on network system voltage
By increasing the VARIAC'S position, you can increase the overvoltage phasing value to the
desired value or to that value at which the network protector breaker will close its main
contacts. The network protector breaker should be closed several times to ensure that the
operation is consistent.