I.B.
35-557
17 of 45
CN-33 MASTER RELAY REVERSE CURRENT TRIP TEST
Before commencing work, refer to the Safety Information.
Switch Positions
Network protector closed, breaker does not have to be in the automatic mode.
FUNCTION Switch – “RELAY” position
I & PV Switch – AI position
Supp VM Switch – CA position
PHASE switch – 180 position
Single PH Test Switch – OFF position
SUPPLY Switch – 216 or 480 position depending on network system voltage
VARIAC – zero position
By increasing the VARIAC’S position you can increase the reverse current value to the desired
reverse current value. The CN-33 master relay reverse current adjustment screw is designed to
interface with a series of three leaf springs hung below the moving contact assembly. By increasing
or decreasing the spring deflection will increase or decrease the trip setting.