DESCRIPTION OF CONTROLS
P1 and P2 – Cable Input Sockets
NOTE – They are polarized and have a different contact arrangement. Dust covers with lanyards
are supplied.
F1, F2, F3 – Test kit fuses, Type KTKR-15.
POWER ON LIGHT – Is illuminated when the supply switch is moved from the “OFF” position to
either the 480 or 216 position.
SUPPLY SWITCH – Marked “216-OFF-480”, should be moved only after all the cable connections
are complete and set to the correct system voltage at the time of testing.
AMMETER – This digital meter shows the reverse current trip value.
VOLTMETER – The digital voltmeter reads system voltage determined by the position of the Supply
Voltmeter Switch. It also reads phasing volts if the phasing volt selector switch is in the ON position
and the I & PV switch is in any one of the PV (A, B, C) selections. NOTE – both digital meters,
upon power-up, go through an initializing sequence that can take several seconds to complete.
The red and green indicator lights are used in conjunction with the “COMM-RED-GREEN” marked
leads. These are intended to be used with dry contacts.
WARNING
DO NOT USE THE LEADS MARKED “COMM-RED-GREEN” ON ENERGIZED CIRCUITS.
PHASING SWITCH – determines the phasing voltage phasor angle with respect to the network
voltage in the “0” and “60” degree position. It also determines the reverse current angle with
respect to the individual phase voltage at either “120”, “180” or “240” degree position.
TEST SWITCH – Relay position is used to test and calibrate network protectors with relays. The
Mech position is used in the mechanical test without relays.
SUPPLY VOLT SWITCH – will monitor the system voltage. It is also used in the mechanical mode
to select either phase-to-phase or phase-to-ground connections.
VARIAC – is used to set the various voltages either phase-to-phase or phase-to-ground during both
mechanical testing and voltage as well as current in the Relay mode.
PHASING VOLT SWITCH – in the ON position permits phasing volts to be displayed on the
voltmeter. In the OFF position will display the system voltage determined by the Supply
Voltmeter Switch position. It should be in the OFF position for all MECH tests.