94
CTC GSi 600
12.9
Settings
This is used to set the parameters for your home’s
heating requirements. It is important that this basic
setting is right for your home. Values which are set
incorrectly may mean that your property is not warm
enough or that an unnecessarily large amount of energy
is being used to heat your property.
12.9.1
Settings Heating circuit*
Max primary fl ow °C
60 (30...70)
Maximum permitted temperature supplied to the
respective heating circuit.
Heating circuit 2 can only give
the same temperature as heating circuit 1 or a lower
temperature.
Min primary fl ow °C
Off (Off/15...65)
You can use this option to set the minimum permitted
temperature if you want a specifi c level of background
heating during the summer in the basement or
underfl oor heating coils, e.g. in the bathroom. The
heating in other parts of your property should then
be switched off using thermostatic radiator valves or
shut-off valves. Note that the radiator pump G2 will then
operate for the whole summer. This means that the
temperature supplied to the radiators will not fall below a
selected temperature, for e27°C.
"Off" means that the function is turned off.
Heating, mode
Auto (Auto/On/Off)
Switching between heating season and summer mode
can take place automatically (Auto) or a selection can be
made here to set the heating to "On" or "Off".
Auto
= switching the heating season On and Off carried
out automatically.
On
= Continuous heating season, the radiator pump
circulates constantly.
Off
= there is no heating, the radiator pump does not
run (is turned over).
Heating mode, ext.
(Auto/On/Off)
The heat mode selected in this menu can be enabled/
disabled externally.
This menu bar is displayed for the current heating circuit
if a remote control input or a weekly schedule has been
defi ned for the function.
Read more in the "Def. Remote Control" section of the
"Installer / Defi ne” chapter.
CTC GSi can control up to 2 heating circuits.
Part of the "Installer/Settings/Heating Circuit/Heating Circuit 1"
menu.
Menu: "Installer/Settings”.
i
First defi ne the desired functions,
see "Installer/Defi ne". Settings are
only displayed for enabled functions.
Содержание GSi 600 Series
Страница 26: ...26 CTC GSi 600 CTC GSi 616 CTC GSi 608 GSi 612 qw l min qw l min 6 1 8 Pressure differential diagram hot side ...
Страница 31: ...31 CTC GSi 600 Y60 B2 G2 Y2 G2 B15 B11 6 1 15 Schematic diagram passive cooling alt 1 common cooling heating ...
Страница 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Страница 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Страница 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Страница 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Страница 131: ...131 CTC GSi 600 ...
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ......
Страница 136: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 58 1 2020 09 16 ...