![CTC Union GSi 600 Series Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/ctc-union/gsi-600-series/gsi-600-series_installation-and-maintenance-manual_2693362011.webp)
11
CTC GSi 600
ºC
ºC
Summer-time operation
All properties have internal heat gains (lamps, oven,
body heat, etc.), which means that the heating can be
switched off when the outdoor temperature is lower
than the desired room temperature. The better insulated
the house is, the earlier the heating from the heat pump
can be switched off.
The example shows the product set at the default value
of 18°C. This value,
"Heating off, outside"
, can be
changed in the "Advanced / Settings / Heat System"
menu.
In systems with a radiator pump, the radiator pump
stops when the heat is switched off. The heating starts
up automatically when it is required again.
Automatic or remote-controlled summer period
The factory setting causes "summer" to commence
automatically at 18ºC, as "Heating mode" is set to
"Auto".
Heating, mode
Auto (Auto/On/Off)
Auto
means automatic.
On
means that the heating is on. For systems with
a mixing valve and a radiator pump, the mixing valve
operates to the primary flow setpoint and the radiator
pump is on.
Off
means that the heating is switched off. For systems
with a radiator pump, the radiator pump is switched off.
Heating, ext. mode
- (- /Auto/On/Off)
Facility for remote control of whether the heating is to be
on or off.
Auto
means automatic.
On
means that the heating is on. For systems with
a mixing valve and a radiator pump, the mixing valve
operates to the primary flow setpoint and the radiator
pump is on.
Off
means that the heating is switched off. For systems
with a radiator pump, the radiator pump is switched off.
- No selection means no function when activated.
Heating up
Heating up
Outside Temperature
Heating off, out
Primary Flow Temperature
Heating
switched
off
Содержание GSi 600 Series
Страница 26: ...26 CTC GSi 600 CTC GSi 616 CTC GSi 608 GSi 612 qw l min qw l min 6 1 8 Pressure differential diagram hot side ...
Страница 31: ...31 CTC GSi 600 Y60 B2 G2 Y2 G2 B15 B11 6 1 15 Schematic diagram passive cooling alt 1 common cooling heating ...
Страница 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Страница 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Страница 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Страница 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Страница 131: ...131 CTC GSi 600 ...
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ......
Страница 136: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 58 1 2020 09 16 ...