8
CTC GSi 600
i
The set heating curve always takes priority. The room sensor can only increase
or decrease the heat beyond the set heating curve to a certain extent. Where
operating without a room sensor, the selected heating curve determines the
flow temperature supplied to the radiators.
The House Heating Curve
The heating curve is the central part of the product’s control system. It is the
heating curve which determines the compensated flow temperature requirements
for your property dependent upon the outdoor temperatures. It is important that
the heating curve is correctly adjusted, so that you achieve the best operation and
economy possible.
One property requires a radiator temperature of 30 °C when the outdoor
temperature is 0 °C, whilst a different property requires 40 °C. The difference
between different properties is determined by the radiator surface area, the number
of radiators and how well insulated the house is.
Adjustment of Default Values for the Heating Curve
You define the heating curve yourself for your property by setting two values in
the product control system. This is achieved by selecting the options Inclination or
Adjustment under the "Installer / Settings / Radiator system" menu. Ask your installer
to help you set these values.
It is extremely important to set the heating curve and, in some cases, unfortunately,
this process may take several weeks. The best way of doing this, upon the initial
start-up, is to select operation without any room sensor. The system then operates
using the outdoor temperature reading and the property’s heating curve only.
During the adjustment period it is important that:
• the night reduction function is not selected.
• all thermostat valves on the radiators be fully opened. (This is to find the
lowest curve for the most economical use of the heat pump).
• the outdoor temperature is not higher than +5 °C. (If the outdoor temperature
is higher when the system is installed, use the factory set curve until the
outdoor temperature falls to a suitable level).
• the radiator system is operational and correctly adjusted between different
circuits.
Your home’s heating settings
Содержание GSi 600 Series
Страница 26: ...26 CTC GSi 600 CTC GSi 616 CTC GSi 608 GSi 612 qw l min qw l min 6 1 8 Pressure differential diagram hot side ...
Страница 31: ...31 CTC GSi 600 Y60 B2 G2 Y2 G2 B15 B11 6 1 15 Schematic diagram passive cooling alt 1 common cooling heating ...
Страница 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Страница 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Страница 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Страница 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Страница 131: ...131 CTC GSi 600 ...
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ......
Страница 136: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 58 1 2020 09 16 ...