![CTC Union GSi 600 Series Скачать руководство пользователя страница 130](http://html1.mh-extra.com/html/ctc-union/gsi-600-series/gsi-600-series_installation-and-maintenance-manual_2693362130.webp)
130
CTC GSi 600
Alarm messages
Description
[E047] Stop, low suct. gas exp.
valve
This message appears when the suction gas temperature is low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E048] Stop, low evap. exp.
valve
This message appears when the expansion valve’s evaporation temperature is
low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E049] Stop, high evap. exp.
valve
This message appears when the expansion valve’s evaporation temperature is
high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E050] Stop, low overheat. exp.
valve
This message appears when the expansion valve’s overheat temperature is
low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E052] Phase 1 missing
[E053] Phase 2 missing
[E054] Phase 3 missing
This message appears in the event of a phase failure.
[E055] Wrong phase order
The product’s compressor motor must rotate in the right direction. The
product checks that the phases are connected correctly; otherwise, an alarm
is triggered. This will require changing two of the phases into the product. The
power supply to the system must be shut off when rectifying this fault. This
fault generally only occurs during installation.
[Exxx] Alarm 'sensor'
An alarm message is displayed if an error occurs with a sensor that is not
connected or has short-circuited and if the value is outside the sensor’s range.
If this sensor is important to the system’s operation, the compressor stops.
This requires the alarm to be reset manually after the fault has been rectified.
The alarm is reset automatically after correction for the following sensors:
Sensor upper tank (B5), Sensor EHS tank (B47), Sensor primary flow 1 (B18),
Sensor primary flow 2 (B2), Sensor out (B15), Room sensor 1 (B11), Room
sensor 2 (B12), Sensor brine out, Sensor brine in, Sensor HPin, Sensor HPout,
Sensor discharge, Sensor suction gas, Sensor high pressure, Sensor low
pressure.
[E057] Motor protect high curr.
High current into the compressor has been detected. Press reset and check
whether the alarm recurs. If the fault recurs, contact your installer.
[E058] Motor protect low curr.
Low current into the compressor has been detected. Press reset and check
whether the alarm recurs. If the fault recurs, contact your installer.
[E061] Max thermostat
This alarm message appears if the product becomes too hot.
During installation, make sure the max. thermostat (F10) has not been
triggered as there is a chance of this occurring if the boiler has been stored
in extremely cold temperatures, Reset it by pressing in the button on the
electrical switchboard behind the front panel.
[E087] Driver
[E088] Driver: 1 -
[E109] Driver: 29 Driver
fault.
[E117] Driver: Offline
Press reset and check whether the alarm recurs.
If the fault recurs, contact your installer and tell them the error code number
where applicable.
Communication error. The electrical connection box and driver of the heat
pump are not communicating.
Содержание GSi 600 Series
Страница 26: ...26 CTC GSi 600 CTC GSi 616 CTC GSi 608 GSi 612 qw l min qw l min 6 1 8 Pressure differential diagram hot side ...
Страница 31: ...31 CTC GSi 600 Y60 B2 G2 Y2 G2 B15 B11 6 1 15 Schematic diagram passive cooling alt 1 common cooling heating ...
Страница 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Страница 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Страница 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Страница 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Страница 131: ...131 CTC GSi 600 ...
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ......
Страница 136: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 58 1 2020 09 16 ...