84
X. Operation
F. Changing Adjustable Parameters (continued)
“Press”
Modulation
Setup
button to access the following parameters:
Factory
Setting
Range / Choices
Parameter and Description
100%
Minimum to
Maximum
Heat Rate
Central Heat Maximum Expected Heat Rate
This parameter defines the highest modulation rate the Control will go to during a central heat
call for heat. If the rated input of the installed home radiation is less than the maximum output of
the boiler, change the Central Heat Maximum Expected Heat Rate (fan speed) setting to limit the
boiler output accordingly.
80%
Minimum to
Maximum
Heat Rate
Domestic Hot Water (DHW) Maximum Expected Heat Rate
This parameter defines the highest modulation rate the Control will go to during a Domestic Hot
Water call for heat. If the rated input of the indirect water heater is less than the maximum output
of the boiler, change the DHW Maximum Expected Heat Rate (fan speed) setting to limit the boiler
output accordingly.
100%
Minimum to
Maximum
Heat Rate
Auxiliary Maximum Expected Heat Rate
This parameter defines the highest modulation rate the Control will go to during the auxiliary heat
call for heat. If the rated input of the Auxiliary Heat Zones is less than the maximum output of the
boiler, change the Auxiliary Heat Maximum Expected Heat Rate (fan speed) setting to limit the
boiler output accordingly.
40%
Minimum to
Maximum
Heat Rate
Zone 1 Expected Heat Rate (typical for zone 1 through 16)
This parameter defines the highest modulation rate the Control will go to during the Zone 1 call for
heat. If the rated input of the installed home radiation in zone 1 is less than the maximum output
of the boiler, change the Zone 1 Expected Heat Rate (fan speed) setting to limit the boiler output
accordingly.
30
Minutes
0 to 60 Minutes
Zone Release Time
After the Zone Release Time minutes and a zone has not been satisfied (thermostat opens) the
measured heat loss will be released to increase to the Central Heat Maximum Heat Rate.
See Table
29
Minimum
- 100 to Maxi
-
mum
Minimum Heat Rate
This parameter is the lowest modulation rate the Control will go to during any call for heat.
See Table
29
See Table 29
Lightoff Heat Rate
This is the blower speed during ignition and flame stabilization periods.
Содержание Phantom-X PHNTM210
Страница 7: ...7 Figure 1B Model PHNTM285 I Product Description Specifications and Dimensional Data continued...
Страница 52: ...52 VIII Electrical continued...
Страница 53: ...53 VIII Electrical continued Figure 26 Wiring Connections Diagram...
Страница 54: ...54 VIII Electrical continued Figure 27 Ladder Diagram...
Страница 59: ...59 Figure 29B Boiler to Boiler Communication with Crown Zone Panel PN 3501505 VIII Electrical continued...
Страница 109: ...109 XIII Repair Parts 1L 1K 1J 1E 1C 1D 1B 1L 1J 1A 1M 1F 1C 1D 1B 1L 1J 1A 1M 1F 1K 1G 1G 1K 1H 1G...
Страница 118: ...118...
Страница 119: ...119...