8
Table 2: Ratings
I. Product Description, Specifications and Dimensional Data
(continued)
Phantom Series Gas-Fired Boilers
Model Number
Input (MBH)
Output
(MBH)
Net AHRI Ratings Water
1
(MBH)
AFUE
(%)
Min.
Max.
PHNTM210
42
210
194
169
95.0
PHNTM285
57
285
262
228
95.0
Ratings shown are for installations at sea level and elevations up to 2000 ft. For elevations above 2000 ft., the boiler will
naturally derate by 2.5% for each 1000 ft. above sea level. Boilers not suitable for use with LP gas above 7000ft.
1
Net AHRI Water Ratings based on piping and pickup allowance of 1.15. The manufacturer should be consulted before
selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation,
extensive piping systems, etc.
II. Unpacking Boiler
CAUTION
Do not drop boiler.
A.
Move boiler
to approximate installed position.
B.
Remove
all
crate fasteners.
C.
Lift and remove
outside container.
D.
Remove boiler
from cardboard positioning sleeve on
shipping skid.
WARNING
Installation of this boiler should be undertaken
only by trained and skilled personnel from a
qualified service agency.
E.
Move boiler
to its permanent location.
Содержание Phantom-X PHNTM210
Страница 7: ...7 Figure 1B Model PHNTM285 I Product Description Specifications and Dimensional Data continued...
Страница 52: ...52 VIII Electrical continued...
Страница 53: ...53 VIII Electrical continued Figure 26 Wiring Connections Diagram...
Страница 54: ...54 VIII Electrical continued Figure 27 Ladder Diagram...
Страница 59: ...59 Figure 29B Boiler to Boiler Communication with Crown Zone Panel PN 3501505 VIII Electrical continued...
Страница 109: ...109 XIII Repair Parts 1L 1K 1J 1E 1C 1D 1B 1L 1J 1A 1M 1F 1C 1D 1B 1L 1J 1A 1M 1F 1K 1G 1G 1K 1H 1G...
Страница 118: ...118...
Страница 119: ...119...