83
X. Operation
F. Changing Adjustable Parameters (continued)
Figure 43: Four Zone House (with Zone Control Connected)
Figure 44: Expected Heat Rate Adjustment (with Zone Control Connected)
Maximum Heat Rate:
Automatically adjusted
by the Control based on
the size and number of
zones calling for heat.
Example “call for heat”
durations for a four zone
house.
Maximum heat rate limits
firing rate and prevents
the Control from firing to
100% in response to a
smaller zone demands.
The Control is shipped with defaults that will provide improved operation. Adjustment is only required to optimize
setup.
The expected heat rate adjustment is used to better match boiler output to the home heating needs. After receiving
a "call for heat" the Control first uses the expected heat rate value to set a maximum heat rate. The maximum heat
rate is the highest heat rate that the boiler can fire to at that moment. The maximum heat rate is the summation of
the expected heat rates for the active (turned on) zones. After establishing the maximum heat rate the Control then
measures water temperature and fires the boiler only as hard as required for the heat demand.
Actual Heat Rate:
Boiler is free to modu-
late based on tempera
-
ture from minimum to
maximum heat rate.
Expected Heat Rate Adjustment Screens (HeatMatch Software)
NOTE
This feature requires Zone
Control to be connected.
Refer to Electrical section for
Zone Control connection infor-
mation.
The sum of Zone Expected
Heat Rates plus DHW Maxi
-
mum Expected Heat Rate
(if DHW is active) is used to
calculate the active maximum
modulation rate.
Maximum modulation num
-
bers are shown in both RPM
and kbtu/hr to allow for easier
understanding of boiler heat
rate.
Содержание Phantom-X PHNTM210
Страница 7: ...7 Figure 1B Model PHNTM285 I Product Description Specifications and Dimensional Data continued...
Страница 52: ...52 VIII Electrical continued...
Страница 53: ...53 VIII Electrical continued Figure 26 Wiring Connections Diagram...
Страница 54: ...54 VIII Electrical continued Figure 27 Ladder Diagram...
Страница 59: ...59 Figure 29B Boiler to Boiler Communication with Crown Zone Panel PN 3501505 VIII Electrical continued...
Страница 109: ...109 XIII Repair Parts 1L 1K 1J 1E 1C 1D 1B 1L 1J 1A 1M 1F 1C 1D 1B 1L 1J 1A 1M 1F 1K 1G 1G 1K 1H 1G...
Страница 118: ...118...
Страница 119: ...119...