90
“Press”
button to access the following parameters:
Factory
Setting
Range / Choices
Parameter and Description
180°F
(82.2°C)
60°F to 190°F
(16°C to 87.8°C)
Auxiliary Heat Setpoint
Target temperature for the Auxiliary Heat priority. Value also used by the outdoor air reset
function.
170°F
(76.7°C)
80°F to 190°F
(26.7°C to 87.8°C)
Auxiliary Heat Thermostat “Sleep” or “Away” Setback Setpoint
Thermostat setback setpoint is used when the EnviraCOM thermostat is in “leave” or “sleep”
modes and sensed at E-COM terminals D, R, and C. When setback is “on” the thermostat set
-
back setpoint shifts the reset curve to save energy while home is in a reduced room temperature
mode. The reset curve is shifted by the difference between the High Boiler Water Temperature
and the Thermostat Setback Setpoint. Honeywell VisionPro IAQ part number TH9421C1004 is a
“setback” EnviraCOM enabled thermostat. When connected, it allows boiler water setback cost
savings.
7°F
(3.9°C)
2°F to 10°F
(1.1°C to 5.6°C)
Auxiliary Heat Diff Above
The boiler stops when the water temperature rises ‘Diff Above’ degrees above the setpoint.
5°F
(2.8°C)
2°F to 25°F
(1.1°C to 14°C)
Auxiliary Heat Diff Below
The boiler starts when the water temperature drops ‘Diff Below’ degrees below the setpoint.
3
1 to 5
Response Speed
This parameter adjusts the Auxiliary Heat temperature controller Proportion Integral Derivative
(PID) values. Higher values cause a larger firing rate change for each degree of temperature
change. If set too high firing rate “overshoots” required value, increases to high fire causing the
temperature to exceed the “Diff Above” setpoint and cycle the boiler unnecessarily. Lower values
cause a smaller firing rate change for each degree of temperature change. If set too low, the
firing rate response will be sluggish and temperature will wander away from setpoint.
Disable
Disable, Enable
Auxiliary Priority Over Central Heat
This parameter allows the Auxiliary Heat demand to be higher or lower priority than Central Heat
demand. When both demands are active at the same time the Control uses the Setpoint, Diff
Above and Diff Below for the demand that has priority.
Disabled Auxiliary Heat is lower priority than Central Heat demand.
Enable Auxiliary Heat is higher priority than Central Heat demand.
Zone
Control
Zone Control,
DHW Terminal
Auxiliary Heat Demand Source
The Control’s “DHW Temp Switch” input terminal may be used as a Domestic Hot Water (DHW)
demand or Auxiliary Heat demand. When the Domestic Hot Water Demand Source is set to
Zone Control and the Auxiliary Heat Demand Source is set to “DHW Terminal” an Auxiliary Heat
Demand may be wired to the DHW Temp Switch terminals. This feature may be used even if a
Zone Control is not installed.
Zone Control
Auxiliary Heat demand may only be wired to the Zone Control
DHW Terminal Auxiliary Heat demand may be wired to the Zone Control or DHW Terminal.
Supply
Sensor
Supply Sensor,
Header Sensor
Modulation Sensor
Heat Demand may respond to the boiler’s Supply Temperature or Header Temperature sensors.
When Header Sensor is selected the boiler is fired in response to the sensor wired to Header
Sensor Low Voltage Terminal Block Terminals.
X. Operation
F. Changing Adjustable Parameters (continued)
Содержание Phantom-X PHNTM210
Страница 7: ...7 Figure 1B Model PHNTM285 I Product Description Specifications and Dimensional Data continued...
Страница 52: ...52 VIII Electrical continued...
Страница 53: ...53 VIII Electrical continued Figure 26 Wiring Connections Diagram...
Страница 54: ...54 VIII Electrical continued Figure 27 Ladder Diagram...
Страница 59: ...59 Figure 29B Boiler to Boiler Communication with Crown Zone Panel PN 3501505 VIII Electrical continued...
Страница 109: ...109 XIII Repair Parts 1L 1K 1J 1E 1C 1D 1B 1L 1J 1A 1M 1F 1C 1D 1B 1L 1J 1A 1M 1F 1K 1G 1G 1K 1H 1G...
Страница 118: ...118...
Страница 119: ...119...