September 2011
46
V1.44
Copyright © 2011 Adept Systems, Inc. and Control Network Solutions Ltd All Rights Reserved.
709.1 packets received
: This is the total number of packets received in from Side A (709.1) by
the router since the statistics were cleared. In Bridging mode this provides the total number of
IP 852 packets received in from Side A.
709.1 packets sent
: This is the total number of packets sent out to Side A (709.1) by the router
since the statistics were cleared. In Bridging mode this provides the total number of IP 852
packets sent out to Side A.
IP packets received
: This is the total number of 852 packets received in from Side B (IP) by the
router since the statistics were cleared. This total includes both all the 852 data packets and the
852 configuration (management) packets.
IP packets sent
: This is the total number of 852 packets sent out to Side B (IP) by the router
since the statistics were cleared. This total includes both all the 852 data packets and all the
852 configuration (management) packets.
852 Data packets received
: This is the total number of 852 Data packets only received in from
Side B (IP) by the router since the statistics were cleared.
852 Data packets sent
: This is the total number of 852 Data packets only sent out to Side B (IP)
by the router since the statistics were cleared.
852 Management packets received
: This is the total number of 852 Management packets only
received in from Side B (IP) by the router since the statistics were cleared.
852 Management packets sent
: This is the total number of 852 Management packets only sent
out to Side B (IP) by the router since the statistics were cleared.
Update Stats
: This button updates the statistics and refreshes the display.
Clear Stats
: This button zeros out the statistics, restarts the statistics time counter and
refreshes the display.
Bootup Log
: This list shows the last ten dates and times that the eNodeIV device has been reset
or power cycled. The first column labelled Power Loss Time shows the time the device was
powered off or reset. The second column labelled BootUp time shows the time the device
rebooted. If the times are identical then the device was reset not power cycled. If the times are
different the difference is the length of time the device lost power.
Clear Boot Log
: This button clears the boot up log and sets all the times and dates to zeros.