September 2011
15
V1.44
Copyright © 2011 Adept Systems, Inc. and Control Network Solutions Ltd All Rights Reserved.
2. Web Configuration
The Web-based eNodeIV device interface allows the user to access and change configuration
data on the eNodeIV device by using any http Web browser attached to the network. This
allows users to make changes to the eNodeIV device remotely. This chapter familiarises the
user with the various pages of the Web-based Interface and describes the steps necessary to
changing configuration data.
2.1. Default IP Configuration
The eNodeIV device is configured through a web browser such as FireFox, Internet Explorer,
Safari, or others. In order to connect to the eNodeIV device from a web browser, the eNodeIV
device and the computer running the web browser must be connected to the same IP network.
The factory default IP host address of the eNodeIV device is 10.0.2.40 with subnet mask of
255.255.255.0. The router's web server is serving http on port 80. The computer running the
web browser must be able to access the eNodeIV device's subnet.
Default Internet Configuration
IP Host Address
10.0.2.40
IP Subnet Mask
255.255.255.0
Web HTTP Port
80
2.1.1. Ethernet
For Ethernet equipped eNodeIV devices, first configure the host computer to add an IP
interface on subnet 10.0.2.0/255. Connect one end of a Cat5 Ethernet cable to the RJ-45 on
the eNodeIV device and the other end to an Ethernet hub or switch or directly to a computer
with a crossover cable or straight through if the computer’s Ethernet port supports auto
crossover (Auto MDIX). The eNodeIV Ethernet port is MDI only. In cases where the LAN does
not support the default subnet, a direct connection between the ENodeIV device and the web
browser host computer will be needed.