September 2011
70
V1.44
Copyright © 2011 Adept Systems, Inc. and Control Network Solutions Ltd All Rights Reserved.
On router B’s
Twin Mode Setup Page
, click the
Sync Data From Twin
button. Router B
should now display router A’s 709.1 (IP and LON CN) subnet/node addresses.
On router B’s
Twin Mode Setup Page
, click the
Sync Data To Twin
button. Router A
should now display router B’s 709.1 (IP and non IP) subnet/node addresses. To verify go
to router A’s router A’s
Twin Mode Setup Page
.
On router B’s
Twin Mode Setup Page
, enable
Twin Mode
by selecting the associated
ON
radio button.
On router A’s
Twin Mode Setup Page
, enable
Twin Mode
by selecting the associated
ON
radio button. The routers will now act as a redundant pair.
Go to the
Twin Status Page
to observe operational state and failure statistics.
The monitoring application on each router is now ready to be commissioned. Repeat the
following steps for each router.
Drag a new device shape onto the LonMaker drawing. The device should be attached to
the channel on the LON side of the eNodeIV device. Setup and commission this device.
Use the SRV App to send a service pin for the monitoring application.
Drag a new functional block onto the LonMaker drawing and associate it with the newly
created device. The status and alarming network variables are now ready to be bound.
The sequence of dialog boxes you will encounter is given below.
Fig.4.7: LonMaker New Device Dialog