Operating Instructions
Insulated Conductor Rail System
SinglePowerLine Program 0813
BAL0813-0007-EN
www.conductix.com
translated document
page 21 of 108
3.3
Unsuitable ambient conditions
The conductor rail must
not be installed
and
not be operated
under these environmental conditions (see also Section 2.5 , Section
◼
Operation at excessively high or excessively low temperatures (Standard: < -10°C, > 55°C, different ambient temperatures on
request).
◼
In environments containing chemical substances or gases that can potentially permanently damage the conductor rail's materials
(corrosion) or drastically impact on the insulation.
◼
In ambient air that contains solvent vapors or aromatic compounds.
◼
In ambient air that contains flammable or explosive gases or dusts.
◼
In flammable or explosive materials in the vicinity, particularly below the conductor rail.
◼
In dusty environments.
◼
Outdoors with free weathering.
◼
In environments with relative humidity of more than 85%.
◼
In close proximity to splashing water.
◼
In environments that require a higher protection class than IP 2X.
WARNING!
Faults due to incorrect operating conditions!
If the operating conditions change or are no longer within the specified range, the conductor rails
can malfunction due to short circuits, premature aging and damage to electrical and mechanical
components.
→
The conductor rail must be disconnected from the power if the operating conditions are no longer
within the permissible range described above.
→
The conductor rail must be disconnected from the power if it gets wet or is soiled. Dry or clean
according to regulations (observe WV0800-0001).
→
Take the relevant measures to restore suitable operating conditions.