Operating Instructions
Insulated Conductor Rail System
SinglePowerLine Program 0813
BAL0813-0007-EN
www.conductix.com
translated document
page 20 of 108
3.1
Installation orientation
WARNING!
Danger due to increased wear or damage!
→
Align the current collector with its central axis exactly on the central axis of the conductor rail
→
The mean distance between the bracket axis and the contact surface must be precisely complied
with.
WARNING!
Loss of contact or increased heating!
Hazard due to loss of contact or increased heating if the current collector is operated outside the
permissible installation position.
3.2
Tolerances
The conductor rail must be installed within the following tolerances. Conductix-Wampfler does not accept any responsibility for the
conductor rail's correct functioning if these tolerances are not observed. In such a case, Conductix-Wampfler does not accept any
liability for problems that arise if the conductor rail system is not functioning correctly.
Conductor rails
X: ± 5 mm
Current collector*
X: ± 100 mm; Y: ± 40 mm
Pressure with which the current collector contacts the rail 28 N (with double current collector: 2x28 N)
*Depending on the current collector type
Fig. 1: Conductor bar 0813 coordinate system
X
Z
Y