Register sequence

Sequential RF programming mode can be used to register RF sensors. Each device is acquired automatically in sequence with its 

own ID. After the control panel has acquired the first sensor, it is ready to acquire the next. If several zone slots are already in use, 

a warning message will appear.

•  Start from zone:
Used to select the initial zone (first zone to be registered). The zone can be selected by pressing the zone number followed by 

Enter, or by selecting it with the arrow keys. After pressing Enter, the system is ready to acquire sensors.

1.  After selecting the zone number, the system waits for acquisition of the sensor with the zone number flashing. 
2.  The installer can now press the registration key on the sensor or remove the battery protector tab, or enter the sensor ID 

code. 

 

»

A short chime confirms that registration has take place correctly. If no devices are detected or no code is entered within 60 

seconds, the error message “Retry?” will appear. The 60-second timer is deactivated as soon as a number key is pressed 

(0 to 9) to enter an ID code.

3.  After all sensors have been registered, press (X) to end the procedure and Enter to confirm.

Register zones

This menu can be used to register zones individually and to program its type, properties and various operating parameters.

•  Select zone:

 

This menu entry is used to select the zone number for the device that is being acquired. The number can be entered 

directly using the keypad, or it can be selected using the Up/Down arrows. The list shows whether the slot is already in 

use (a zone has already been registered to it) or whether it is available. The system will always suggest the first available 

position with a logic of filling available spaces.

◊  ID acquisition 

If you press “Enter” after selecting the device number, the system waits for acquisition of the device with the zone 

number flashing. The installer can now press the registration key on the sensor or remove the battery tab, or enter the 

sensor ID code. If no devices are detected or no code is entered within 60 seconds, the error message “Retry?” will 

appear. The 60-second timer is deactivated as soon as a number key is pressed (0 to 9) to enter the ID code. If the 

device has several inputs, the first index (input “A”) is shown. After the device has been registered, a short chime sounds 

and configuration continues.

◊  Zone description 

This menu entry is used to enter a description for the acquired zone. The default name for the zones is "zone xx A/B/C", 

where A/B/C depends on the zone input index.

◊  Zone type 

This menu entry is used to set a zone type for the acquired zone. Refer to the table below for available options. Some 

options require addition information to be entered in order to work properly. If additional settings are required for an 

option, the “up arrow” will display these sub-options instead of continuing to the next configuration step.

Содержание KSW3207LU

Страница 1: ...TECHNICAL MANUAL EN SECUR HUB...

Страница 2: ...ware sett 52 False code 53 Alarm reset 53 Memory reset 53 Save log in out 53 Menu timeout 54 FW download 54 Walk Test opt 55 Chime duration 55 Warning This Comelit product was designed for use in the...

Страница 3: ...plate 2 1 2 3 1 4 5 8 7 6 10 11 9 1 LCD CAP SENSE front panel 2 Microphone 3 Micro USB connectors 4 Battery 5 Battery connector 6 Loudspeaker 7 2G 3G module connector 8 Tamper switch 9 RJ45 Ethernet c...

Страница 4: ...4 Installing the LAN module Installing the 2G 3G module 2 1 2 1 3 2 1 Replacing the backplates...

Страница 5: ...ation channels you intend to use the control panel should be fitted so as to offer good GSM or WiFi signal strength You will need to consider the availability of electricity mains and Ethernet connect...

Страница 6: ...6 Installing the wall mounting backplates Installing the desk base 2 1 3 2A 1A 3A 2 1 3 5 4 6...

Страница 7: ...the system is armed steady or that it is not ready to arm flashing Orange LED indicates a fault in the system steady or the presence of isolated bypassed zones flashing Red LED indicates an alarm tam...

Страница 8: ...stallation wizard is configuring the GSM 3G module if installed f Enter the menu by pressing Enter Confirm f Enter the SIM number using the alphanumeric keypad and confirm when you have finished by pr...

Страница 9: ...n the area to search for all available SSIDs f Select the desired network using the navigation keypad and confirm with Enter Confirm If the network is password protected the control panel will ask you...

Страница 10: ...ve an IP address automatically Set manually If you select the manual option use the alphanumeric keypad to enter the IP address and press Enter Confirm Set date time The fourth step in the installatio...

Страница 11: ...allowing the user to disarm the system before an alarm is triggered The exit time is the time available once the entry exit zone has been closed following system arming to prevent the alarm from bein...

Страница 12: ...one activation will start the Entry delay 1 time program for the selected area This zone type can only activate an alarm if the exit time has elapsed Access This zone type allows the user to activate...

Страница 13: ...sing the navigation keypad and confirm with Enter Confirm Set Sounders The seventh step in the installation wizard is used to register RF sounders 1 Enter the menu by pressing Enter Confirm 2 Select t...

Страница 14: ...the user to add using the navigation keys and confirm by pressing Enter Confirm If the user has already been registered the menu 1 Reset 2 Delete will be available f Enter the code for the user using...

Страница 15: ...p in the installation wizard is used to register accounts relating to the Comelit app on the control panel 1 Enter the menu by pressing Enter Confirm 2 The display shows the first position AppID free...

Страница 16: ...or USA standards The option can also be disabled NTP server enable disable options and addresses are available for up to four NTP servers Event log The control panel can log up to 1024 events New eve...

Страница 17: ...t which the event occurred Date Date on which the event occurred Who User or device that generated the event Area Area in which the event occurred Where Device on which the event was generated EventID...

Страница 18: ...2 standard will be available soon Delete access codes If you confirm this function restores the user and installer access codes to the factory values If you do not confirm the default settings will n...

Страница 19: ...s and the message Found appears To find a device f Move on to the Find RF device menu using the navigation keypad and enter the menu by pressing Enter Confirm f Go to the type of device to find using...

Страница 20: ...new firmware versions which may be available in the Cloud Bear in mind that the control panel may be set to install new versions automatically as soon as they are available in the Comelit Cloud The wa...

Страница 21: ...hen the entry time has elapsed The built in sounder is activated during this additional entry delay period At the end of this entry delay extension the system triggers a full alarm condition the exter...

Страница 22: ...each system Default 3 min Double zone If a zone has the Double zone attribute an alarm will only occur if another zone with the Double zone attribute assigned to the same area is triggered within thi...

Страница 23: ...dates or date periods Select holiday is used to select the holiday you wish to edit create Holiday description is used to enter a description for the holiday Date interval 1 If the second date interva...

Страница 24: ...menu can be used to assign scheduled programs to scheduled armings users outputs or macros Assign to scheduled arming Select schedule programming the scheduled program to be assigned to a scheduled ar...

Страница 25: ...emises that an auto arming procedure is about to be activated This period of time can be set to between 0 and 60 minutes Extraordinary no This menu is used to set the maximum number of times an extrao...

Страница 26: ...sed to scroll through all possible functions and ENTER alternates between YES NO enabling or disabling the function for that profile Restore default this menu restores the default values for the selec...

Страница 27: ...so be used to program sensor settings Programming wireless zones The control panel recognises individual devices each device must be registered in a single zone within the system Each device has a sin...

Страница 28: ...zone This menu entry is used to select the zone number for the device that is being acquired The number can be entered directly using the keypad or it can be selected using the Up Down arrows The list...

Страница 29: ...occurs at any other time Light 1 After the zone is programmed an output number must be programmed such as exit light 1 in the exit menu This only applies to wired outputs Light 2 After the zone is pr...

Страница 30: ...al alarm Gas Gas zones are always active Gas zones generate a gas alarm Flooding Flooding zones are always active Flooding zones generate a water presence alarm The RFH2O device is configured by defau...

Страница 31: ...rm zone the only difference is that a specific alarm event will be sent to the alarm receiving centre Ent T P1 P2 Zones with this attribute will only launch the entry delay if violated during partial...

Страница 32: ...his menu entry is used to assign one or more cameras to the zone for video alarm verification Delete zone this menu is used to delete a zone from the control panel memory A message DELETE ZONE XX will...

Страница 33: ...quisition time used to set the time interval within which the alarm pulses will be taken into account Configuration includes a setting for the Units seconds or minutes and a unit multiplier Alarm puls...

Страница 34: ...HT key LEFT key The direction keys should be associated with a number and the corresponding action can be selected in the same way as the F keys The direction key combination is activated by pressing...

Страница 35: ...buzzer sound if arming was not successful Show status This menu is used to set the period of time after which the system status is removed from the display The possible options are as follows Unlimit...

Страница 36: ...em waits for acquisition of the device with the output number flashing The installer can at this point register the sounder or enter the ID code for the device See appendix A If no devices are detecte...

Страница 37: ...the alarm Zone status The output follows the status of the zones Remote output 1 After programming an output with this type you need to confirm a time between 0 and 255 sec 0 indicates that the output...

Страница 38: ...f default then the down arrow Command URL This menu is used to edit and or enter a URL command that is an HTTP string generated by third parties and copied in the corresponding Sounder Output menu she...

Страница 39: ...be entered directly using the keypad or it can be selected using the arrows The system will always suggest the first available position with a logic of filling available spaces Edit repeater Descript...

Страница 40: ...eys can be used to enter the number directly Default setting 1 Areas description Select area This menu is used to enter a description for the area and for its partitions P1 and P2 The default name for...

Страница 41: ...e selected recipient Entering an email address automatically enables the email protocol for that recipient IP address this menu option is used to enter the IP address of the selected recipient This me...

Страница 42: ...ion report the first event group is shown at the top of the display for example Alarms group There are 16 positions corresponding to the positions of the addresses of the first 16 recipients at the bo...

Страница 43: ...ng event Technical programming used to customise voice messages for the technical programming event System operation group used to customise voice messages for each group event Exclude zone group used...

Страница 44: ...quired The possible options are as follows Handshake Yes Kissoff Yes Handshake Yes Kissoff NO Handshake NO Kissoff Yes Handshake NO Kissoff NO The default setting is NO NO TWO WAY audio User audio use...

Страница 45: ...tandard DC 09 Manual test This menu is used to select which recipients will be made available in the Communications test user menu Enabled recipients can be tested manually here via the Communications...

Страница 46: ...mail header can be entered here The text scrolling function allows entry of up to 50 characters Backup this menu is used to enable the email App and ARC backup channel The backup channel is 3G for pro...

Страница 47: ...l panel to a WiFi network You can browse a list of available networks using the Up Down arrows and after selecting the correct network enter the password A confirmation message is shown after connecti...

Страница 48: ...ing entry time when the option is disabled no buzzers will be activated during entry time Exit buzzer the buzzer is activated during exit time when the option is disabled no buzzers will be activated...

Страница 49: ...the arming program to be created or edited The UP DOWN arrow can be used to move through the list ENTER is used to access the arming program configuration steps Description this menu entry is used to...

Страница 50: ...val from 00 01 to 23 59 Default 21 min Anti jam RF network jamming interference can be detected by the control panel The detection function can be enabled or disabled using this menu entry Green LED T...

Страница 51: ...p to 10 Macros Each macro can trigger 15 actions The actions may be as follows Arm system Disarm system HH MM wait time in hours and minutes before continuing to the next step MM SS wait time in minut...

Страница 52: ...Wait MM SS wait time in minutes and seconds before continuing to the next action Output ON activation of an output Output OFF deactivation of an output URL commands Please refer to Radio outputs on pa...

Страница 53: ...soon as the sounder audible alert emission time has elapsed Code When this option is selected the system will reset the alarm as soon as a valid disarming code is entered on the system Memory reset T...

Страница 54: ...install As with the previous option but without limitations on the download channel which can also be 3G TCP auto downl With this option selected the system will automatically check whether new firmw...

Страница 55: ...zone is confirmed via an audible signal Indoor sounder activation of the walk test zone is confirmed via a short audible signal emitted by the indoor sounder External sounder activation of the walk te...

Страница 56: ...2 a edizione 06 2022 cod 2G40002649 w w w c o m e l i t g r o u p c o m Via Don Arrigoni 5 24020 Rovetta BG Italy C E R T I F I E D M A N A G E M E N T S Y S T E M S...

Отзывы: