C3G-SCC2 SERVO CONTROL CPU
The Servo Control CPU manages axes movement control in a machine receiving the trajectory targets from the RBC module, through
the VME bus in the master-slave mode and microinterpolating the trajectories themselves; it sends information about machine status
and any alarms to the RBC module, also through the VME bus.
The SCC2 module is interfaced with the machine for transmitting the resolver energising signal and resolver reading, and with the
Servo Amplifiers Unit 2 for transmitting current references.
The SCC2 module interface towards the Servo Amplifiers Unit is modular; in fact, on the SCC2 it is possible to install up to four AXIS I/O
annexes; each AXIS I/O annex reads the position and generates the current reference for two motors.
The Servo Control CPU manages up to 8 axes, also subdivided on two arms, as it possesses two interpolators. The RAM storage in-
stalled on the SCC2 module also has an external backup battery supply capable of retaining data for at least 1000 consecutive hours;
there is also a condenser for powering the SCC2 module RAM for about one hour in the event of a power failure (also of the backup bat-
tery) which makes it possible to remove the module from the Control Unit for any maintenance operations and/or installation of 22’
DIFF.2-AXIS I/O INTERFACE annex.
FRONT PANEL
MEANING
LED
Colour
Description
PRG
GREEN
When on indicates that the module is in the operating condition.
RUN
GREEN
Turns on at the end of the diagnostic tests performed by the microprocessor
if no module operating faults have been located.
WDG
RED
Turns on after the cutting in of the watchdog circuit for microprocessor
malfunctioning.
BMS
GREEN
This is on when the SCC module performs VME Bus Master functions.
SYF
RED
Turns on when an error is detected at VME bus or VME master board
(SYSFAIL) level.
SFT
RED
Turns on when the safety chain relay opens.
SCC Module connectors
Connector
Pin no.
Functions
J3
male 15
To resolvers of axes 7 - 8
J4
male 50
To resolvers of axes 1 to 6 and serial line RS485 towards RPT
J5
female 50
Analogue signals to SAM modules; serial line RS485 to SAM modules;
safety chain
J6,J7,J8,J9
female 40
Connectors for analogue signals from and to AXIS I/O ANNEX
J6 axes 1-2
J7 axes 3-4
J8 axes 5-6
J9 axes 7-8
J10,J11
female 40
Connectors for digital signals J12, J13 from and to AXIS I/O ANNEX
J10 axes 1-2
J11 axes 3-4
J12 axes 5-6
J13 axes 7-8
P1
male 96
VME BUS CONNECTOR
REPLACEMENTS
Specific cautions:
·
Comply with the “GENERAL RULES FOR MAINTENANCE” given in this chapter.
·
Remove/insert the module avoiding damaging the components (annex) assembled on it.
·
Before replacing the module save the RAM DISK contents (see paragraph SUBSEQUENT SYSTEM SOFTWARE LOADING
WITH SAME SOFTWARE VERSION - SYSTEM SOFTWARE of this chapter).
·
The module removed from the Control Unit rack can keep the data in storage for 1 hour.
·
If the module is replaced the operating system resident on it is lost and it is necessary to reload it after inserting the new module.
·
The jumpers on the module must not be moved or removed.
Special tools:
unnecessary
C3G
Plus
MAINTENANCE
07/1200
7-45
LAYOUT
CONTROL
UNIT
C3G-SCC2
Содержание C3G Plus
Страница 6: ...This page has been intentionally blank UPDATING LIST C3G Plus D 08 0702 ...
Страница 7: ...C3G Plus PREFACE 05 1199 i PREFACE C3G Plus VERSIONS SDLP SDMP SDHP C3G Plus VERSIONS DDMP DDHP ...
Страница 14: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Страница 22: ...This page has been intentionally blank SAFETY REGULATIONS C3G Plus 1 8 02 1299 SAFETY REGULATIONS ...
Страница 24: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Страница 26: ...This page has been left intentionally blank INSTALLATION C3G Plus 2 ii 01 0498 SUMMARY ...
Страница 48: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Страница 61: ...SAMPLE CONNECTION OF C3G EMC2 C3G Plus OPERATOR INTERFACE 07 1200 3 13 EMERGENCY CONTROL C3G EMC2 ...
Страница 120: ...This page has been left intentionally blank OPERATOR INTERFACE C3G Plus 3 72 05 1199 C3G Plus KIT IVECO ...
Страница 122: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Страница 127: ...C3G Plus INTEGRATION GUIDE 06 0400 4 5 SYSTEM I O ...
Страница 143: ...Additional I O modules C3G Plus INTEGRATION GUIDE 01 0498 4 21 parallel i o additional modules ...
Страница 158: ...This page has been intentionally blank INTEGRATION GUIDE C3G Plus 4 36 06 0400 SERIAL I O AND PDL2 TOOLS ...
Страница 160: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Страница 182: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Страница 188: ...This page has been intentionally blank Operations and Maintenance Manual C3G Plus ...
Страница 190: ...This page has been left intentionally blank MAINTENANCE C3G Plus 7 ii 00 1097 GENERAL RULES ...
Страница 192: ...This page has been left intentionally blank MAINTENANCE C3G Plus 7 2 00 1097 PREVENTIVE MAINTENANCE ...
Страница 195: ...Main C3G Plus Connections C3G Plus MAINTENANCE 08 0702 7 5 FUNCTIONAL LAYOUTS C3G Plus sdlp sdmp sdhp VERSIONS ...
Страница 198: ...Axes Control Circuit MAINTENANCE C3G Plus 7 8 00 1097 FUNCTIONAL LAYOUTS C3G Plus sdlp sdmp sdhp VERSIONS ...
Страница 205: ...Power Supply Distribution Page 1 of 2 C3G Plus MAINTENANCE 01 0498 7 15 FUNCTIONAL LAYOUTS C3G Plus ddmp VERSIONS ...
Страница 206: ...Power Supply Distribution Page 2 of 2 MAINTENANCE C3G Plus 7 16 01 0498 FUNCTIONAL LAYOUTS C3G Plus ddmp VERSIONS ...
Страница 207: ...Machine 1 Axes Control Circuit C3G Plus MAINTENANCE 01 0498 7 17 FUNCTIONAL LAYOUTS C3G Plus ddmp VERSIONS ...
Страница 208: ...Machine 2 Axes Control Circuit MAINTENANCE C3G Plus 7 18 04 0799 FUNCTIONAL LAYOUTS C3G Plus ddmp VERSIONS ...
Страница 209: ...Serial and Parallel Line Connections C3G Plus MAINTENANCE 04 0799 7 19 FUNCTIONAL LAYOUTS C3G Plus ddmp VERSIONS ...
Страница 221: ...SAFETY CIRCUIT TEST DEVICES Connector X113 test device C3G Plus MAINTENANCE 04 0799 7 31 diagnostic C3G Plus ...
Страница 225: ...X30 connector test device C3G Plus MAINTENANCE 01 0498 7 35 diagnostic ...
Страница 232: ...This page has been left intentionally blank MAINTENANCE C3G Plus 7 42 00 1097 CIRCUIT DIAGRAMS ...
Страница 255: ...SOFTWARE OPERATIONS FOR CONTROLLER REPLACEMENT 2 2 C3G Plus MAINTENANCE 01 0498 7 65 SYSTEM SOFTWARE ...
Страница 264: ...This page has been intentionally blank 7 74 08 0702 MAINTENANCE C3G Plus LIST OF SPARE PARTS ...
Страница 265: ...OPERATOR S NOTES C3G Plus NOTES ...
Страница 266: ...C3G Plus NOTES ...