ID-FLX Lite & Telecom Global Guide
98
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
0 .. 10 [-]
Default value
-
Step
1
Comm object
11475
Related applications
Description
The second RPM (RPM-BI3 value) can be measured in limited frequency range 1 to 50 Hz on Binary input 3.
The RPM-BI3 value indicates RPM calculated from BI3 frequency and Basic settings: GearTeeth3 setpoint.
The RPM-BI3 value =0 below 1 Hz and =### over 50 Hz.
Configure BI Type = Not used and change the name according the function for RPM-BI3 measuring.
Note:
The RPM-BI3 measuring is switched off when Basic setting: GearTeethBI3 = 0. In this case BI3
operates as standard Binary input.
GearTeethBI3