ID-FLX Lite & Telecom Global Guide
100
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[OFF, MAN, AUT]
Default value
-
Step
-
Comm object
8315
Related applications
Description
Equivalent to Controller mode changes by MODE→ or ←MODE buttons.
Note:
Controller Mode change can be separately password protected.
ControllerMode
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[ENABLED, DISABLED]
Default value
-
Step
-
Comm object
9983
Related applications
Description
DISABLED
Controller stays in AUT mode after Fault reset. Default state.
ENABLED
Automatic switch from AUT to MAN mode after Fault reset to avoid automatic engine start.
This function is active for Shut down protection only.
FltResGoToMAN
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
0 .. 60 [min]
Default value
0 … means that the
display lights all the
time
-
Step
1 [min]
Comm object
10121
Related applications
Description
The display backlight is switched off after timeout.
DispBacklightTO
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[Nom/Idle, N/I Init, Conveyor, RegReqst, R RegDis, CloseLoad, Toggle]
Default value
-
Step
-
Panel Button
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...