143
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U16]
Default value
10
-
Step
1
Comm object
9272
Related applications
Description
Shutdown limit level for AIN4.
AIN4 Level 2
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
10
-
Step
1
Comm object
9273
Related applications
Description
Delay for Wrn/Sd AIN4 alarm.
AIN4 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
NORMAL, CLASS C [-]
Default value
NORMAL
-
Step
-
Comm object
13372
Related applications
Description
NORMAL
Protection behaves according to the standard configuration of Wrn/Sd alarm in
LiteEdit AINx configuration screen. Default state.
CLASS C
The protection is type “Running only” and does not depend on Running only tick
in LiteEdit AINx Alarm properties configuration window. Protection (Class C) is
working after AINx Del or sooner when appropriate value increases over AINx
Wrn limit +3 seconds – after engine start. Warning/ShutdDown protection is
activated with fix delay 0.5 s.
Note:
Class C protection is working and corresponding setpoints are visible only when corresponding
AIN is configured in Modify->Alarm properties-> Direction-> Window prot.
AIN4 Eval
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...