![ComAp ID-Lite Скачать руководство пользователя страница 137](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907137.webp)
ID-FLX Lite & Telecom Global Guide
137
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
10
-
Step
1
Comm object
8264
Related applications
Description
Max time limit of horn sounding. Set to zero if you want to leave the output HORN open. Horn timeout starts
again from the beginning if a new alarm appears before previous Horn timeout has elapsed.
Horn timeout
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
50 .. 150 [%]
Default value
120
YES
Step
1
Comm object
13340
Related applications
Description
Limit for engine ShutDown overspeed protection. Protection is active during start process of the engine and
Idle time.
Note:
The engine can spasmodically reach higher than
level during start, but for
normal running state would be this protection too high. This setpoint allows the overspeed protection
during irregular starting condition.
StartOverspeed
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
50 .. 150 [%]
Default value
115
-
Step
1 % of
Comm object
8263
Related applications
Description
Limit for engine ShutDown overspeed protection.
Overspeed
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
.. 100 [%]
Default value
25
-
Step
1 % of
Underspeed
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...