![ComAp ID-Lite Скачать руководство пользователя страница 131](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907131.webp)
ID-FLX Lite & Telecom Global Guide
131
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
-10000 .. +10000 [-]
Default value
0
YES
Step
1
Comm object
11840
Related applications
Description
Limit to open the
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
Reg CMP Off
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
Reg Bias, LBi SpdUp/Dwn, CU AI1-CU AI9, AIO: AI1 - 4 [-]
Default value
Reg Bias
YES
Step
-
Comm object
13068
Related applications
N/A
Description
The setpoint is used for selecting what regulation will be used in AUTO mode in case automatic regulation is
disabled by
Disable. The options are:
Reg Bias – speed request will be set according to
, this function was standard
functionality of R Reg disable LBI in previous FW versions.
/
– it is possible to regulate speed manually by
/
even in Auto mode.
CU AI1-CU AI9, AIO: AI1 - 4 – it is possible to regulate speed manually by analog inputs even in Auto
mode
Note:
See
AUT SpdReq
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...