ID-FLX Lite & Telecom Global Guide
57
State
Condition of the transition
Action
Next state
RPM = 0 or any other shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
READY TO LOAD off
Shutdown
Cooling
Cooling time elapsed
FUEL SOLENOID off
STOP SOLENOID on
Stop
RPM = 0 or any other shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
Shutdown
Start request
READY TO LOAD on
Running
Stop
RPM<2, Oil pressure not detected, D+ not active
Ready
STOP time Setpoint e 10 s elapsed
Stop (Stop fail)
Note:
1
The start-up sequence can be interrupted in any time by coming stop request
2
Fuel solenoid is switched on with advance of 1 s fixed before starter motor is switched on.
Note:
Threshold level for D+ input is 80% supply voltage; activation delay is 1 s (to override short firings during
cranking – for example in cold conditions).
Speed request:
Engine speed is constant or set manually using Engine params setpoints and Binary inputs.
5.15.5 AUT mode
The controller does not respond to START, STOP buttons. Engine start/stop request is given by binary input
REM START/STOP.
Engine speed request is sourced from PI loop (see below function 3) in AUT mode.
PI loop and Hysteresis comparator functions can be used both for Engine Load Limitation or any other control
function.
Speed request:
Engine speed is adjusted automatically by internal PID loops (when active) - Regulator setpoints group.
5.15.6 Engine without pickup operation
The RPM pickup input is ignored when
= 0. The engine running state is then detected
based on
or
= ENABLED.
signal can be analog or binary. Even the binary signal is to be connected to AIN1
input. In LiteEdit, window Modify, input Oil Pressure, check off the option Binary. The setpoint
set to 1.
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...