ID-FLX Lite & Telecom Global Guide
202
Related FW
2.5.0
Related applications
Comm object
1260
Description
Output closes if engine is running and D+ input not energized.
The output opens, if:
Alarm is not active and
FAULT RESET is pressed
Note:
Threshold level for D+ input is 80% supply voltage.
ChrgAlternFail
Related FW
2.5.0
Related applications
Comm object
339
Description
Output closes when the engine has to be stopped, but speed or oil pressure is detected. This protection goes
active 60s after stop command.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Stop failed
Related FW
2.5.0
Related applications
Comm object
779
Description
Output closes if the engine over speed alarm activates.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Overspeed