Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100.0 .. +1000.0 [Bar]
Default value
2.0
-
Step
0.1
Comm object
8369
Related applications
Description
Warning limit level for ANALOG INPUT 1.
AIN1 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100.0 .. +1000.0 [Bar]
Default value
1.0
-
Step
0.1
Comm object
8370
Related applications
Description
Shutdown limit level for ANALOG INPUT 1.
AIN1 Level 2
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
3
-
Step
1
Comm object
8365
Related applications
Description
Delay for ANALOG INPUT 1.
Note:
Analog input 1 is usually determined to Oil Pressure measurement and it is resistive type of input
with range 0-2500 Ω.
AIN1 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100 .. 10000 [°C]
Default value
80
-
Step
1
Comm object
8375
Related applications
Description
Warning limit level for ANALOG INPUT 2.
AIN2 Level 1
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...