9.2.5 IL-NT GPRS (optional card)
Plug-in into ID-Lite controller COMMUNICATION MODULE port.
Quad Band
850 / 900 / 1800 / 1900 MHz
GPRS multi-slot
class 10
CSD communication
up to 14.4 kbps
TCP/IP communication
over GPRS
Voltage supply 8-36 V DC
9.2.6 IL-NT AOUT8 (optional card)
Plug-in into ID-Lite controller EXTENSION MODULE port.
Number of PWM outputs
8
PWM frequency
1200 Hz
Maximum current
0.5 A
Maximum switching voltage
36 V DC
Output resistance
1 Ω
Resolution
10 bits
9.2.7 IL-NT AIO (optional card)
Plug-in into ID-Lite controller EXTENSION MODULE port.
Resolution
10 bits
Number of Analog inputs
4 (2400 Ω, 20 mA, 4 V)
Maximal resistance range
2400 Ω
Maximal voltage range
4 V
Current range
0-20 mA
Input impedance (current)
180 Ω for mA measuring
Input impedance (voltage)
˃68 kΩ for V measuring
Resistance measurement tolerance
±2 % ±2 Ω
Voltage measurement tolerance
±1 % ±1 mV
Current measurement tolerance
±2 % ±0.2 mA
Number of Analog outputs
1 (21 mA, max.load 100 Ω; 4.6 V, max.10 mA;
PWM 500 Hz (5 V / 10 mA)
Voltage measurement tolerance
±1.5 % ±10 mV
Current measurement tolerance
±2 % ±0.1 mA
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...