ID-FLX Lite & Telecom Global Guide
39
Analog input
R1
R2
Curve
0 – 10 V
150 Ω [1 %, 0.5 W]
100 Ω [1 %, 0.5 W]
AI 0-10 V.CRV
0 – 30 V
680 Ω [5 %, 2 W]
100 Ω [1 %, 0.5 W]
AI 0-30 V.CRV
4 – 20 mA
R = 160 Ω [1 %, 0.5 W]
AI 4-20 mA.CRV
Recommended values
IMPORTANT: Please note that external resistors disconnection, connection incorrect resistors or
input voltage value during operation may cause an analog input destruction.
Example:
VDO pressure sensor 0 – 6 bar with linear voltage output 0 – 10 V
Vout [V]
0
1
2
3
4
5
6
7
8
9
10
P [bar]
0
0.6
1.2
1.8
2.4
3
3.6
4.2
4.8
5.4
6
Conversion table
Modify one of analog input in LiteEdit configuration and load curve AI 0-10 V.CRV
Than you can change resolution and measured value name witch is default displayed at V (volts).
For example if you have connected pressure sensor and his output voltage is 5 V for pressure 3 bar you can
change value ‘V’ in column “Dim:” to ‘Bar’ and by sensor specification adjust all corresponding values in this
column. In this case you can change the value at row 6. from 5 to 3.
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...