Comm object
11847
Related applications
Description
This setpoint is giving regulator integration factor. See Note below.
Note:
ID-Lite controllers include PI loop for speed or analog output regulation. The requested value is
given by setpoints
and
. This loop is working like
Proportional-Integral regulation with setpoints
and Reg Integral for each part and
these parts affect each other.
The controller output is given by:
Reg Gain * e(t) + Reg Integral * ʃ e(t) dt,
where e(t) is deviation of actual value e(t) = Request 1, 2 – Measured value.
Here are two tunning parameters that can be adjusted Reg Gain and Reg Integral. These parameters
interact each other, see the graphic below. Picture shows how differences in Gain and Integral can affect
PI loop’s responsiveness. The central pic is as base case with fast change with minimum oscillations to
required level. Upper left graph shows high gain and low integral values, what produce large oscillation
with slow smoothing. Opposite case is on the lower right graph, which shows low gain and high integral
values. The response of the system is sluggish.
Содержание ID-Lite
Страница 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Страница 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Страница 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Страница 40: ...ID FLX Lite Telecom Global Guide 40 When you finish with adjusting the values click OK and Write to controller...
Страница 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Страница 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...