ID-FLX Lite & Telecom Global Guide
132
Group: Load limit
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
RPM, ECU:Load, CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7,
CU:AI8, CU:AI9, AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4 [-]
Default value
RPM
YES
Step
-
Comm object
11850
Related applications
Description
This setpoint is for Load limit PI loop analog input selection. Source can be adjusted from controller RPM
pick-up, ECU, analog inputs or from extension module inputs.
Load input
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
0 .. 10000 [-]
Default value
0
YES
Step
1
Comm object
11851
Related applications
Description
Constant Load limit PI regulator output. Load Bias is activated when:
Engine Sd protection is activated
= closed
Load input value is invalid (Sensor Fail)
Load Bias